Omron Q2V Series Technical Manual page 349

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

H1-xx: MFDI Function Select
Setting Value
Function
0
Through Mode
1
Forward Run
2
Reverse Run
3
Run Command
4
FWD/REV Cmd
5
3-Wire Seq.
6
Jog Reference
7
Jog Forward
8
Jog Reverse
9
Ext Ref 1/2
A
MultSpd Ref1
B
MultSpd Ref2
C
MultSpd Ref3
D
MultSpd Ref4
E
Offset Frq 1
F
Offset Frq 2
10
Offset Frq 3
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 2 [Reverse Run] at the same
time.
ON : Forward Run
OFF : Run Stop
Note:
• Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm
EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal DI1.
• This function will not operate at the same time as H1-xx = 3, 4 [Run Command, FWD/REV Cmd].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 1 [Forward Run] at the same
time.
ON : Reverse Run
OFF : Run Stop
Note:
• Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm
EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal DI2.
• This function will not operate at the same time as H1-xx = 3, 4 [Run Command, FWD/REV Cmd].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 4 [FWD/REV Cmd] at the same time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 1, 2 [Forward Run, Reverse Run].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 3 [Run Command]
together.
ON : Reverse run
OFF : Forward run
Note:
This function will not operate at the same time as H1-xx = 1, 2 [Forward Run, Reverse Run].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the direction of motor rotation for 3-wire sequence.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG Frequency Reference
(JOG command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to operate the motor in reverse at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
ON : b1-15 [Freq. Ref. Sel. 2], b1-16 [Run Comm. Sel 2]
OFF : b1-01 [Freq. Ref. Sel. 1], b1-02 [Run Comm. Sel 1]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to add the offset frequency set in d7-01 [Offset Frq 1] to the frequency reference when the
terminal activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to add the offset frequency set in d7-02 [Offset Frq 2] to the frequency reference when the
terminal activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to add the offset frequency set in d7-03 [Offset Frq 3] to the frequency reference when the
terminal activates.
Description
11.9 H: TERMINALS
Ref.
569
570
570
570
570
571
571
572
572
572
572
572
573
573
573
573
573
349