Three-Phase 400 V Class - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

3.15 Protect the Drive during Failures
Maximum Applicable Motor Output
Drive Model
ND
B004
0.75 (3/4)
B006
1.1 (1.5)
B010
2.2 (3)
B012
3.0 (3)
B018
-

Three-Phase 400 V Class

Table 3.22 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Maximum Applicable Motor Output
Drive Model
ND
4001
0.37 (1/2)
4002
0.75 (1)
4004
1.5 (2)
4005
2.2 (3)
4007
3.0 (4)
4009
4.0 (5)
4012
5.5 (7.5)
4018
7.5 (10)
4023
11.0 (15)
4031
15.0 (20)
4038
18.5 (25)
4044
22.0 (30)
4060
30.0 (40)
96
kW (HP)
HD
0.55 (1/2)
1.1 (1)
1.5 (2)
2.2 (3)
4.0 (5)
kW (HP)
HD
0.37 (1/2)
0.55 (3/4)
1.1 (2)
1.5 (3)
2.2 (3)
3.0 (4)
4.0 (5)
5.5 (10)
7.5 (10)
11.0 (15)
15.0 (20)
18.5 (25)
22.0 (30)
Semiconductor Protection Fuse Rated Current
Time Delay Fuse
Class J, T, and CC Fuse
Rated Current
A
10
15
25
30
-
Semiconductor Protection Fuse Rated Current
Time Delay Fuse
Class J, CC, and T Fuse
Rated Current
A
3
6
10
10
15
20
25
-
-
-
-
-
-
Manufacturer: EATON/Bussmann
Input Rated Current
Model
A
FWH-60B
60
FWH-80B
80
FWH-100B
100
FWH-125B
125
FWH-150B
150
Manufacturer: EATON/Bussmann
Input Rated Current
Model
A
FWH-40B
40
FWH-40B
40
FWH-50B
50
FWH-70B
70
FWH-70B
70
FWH-90B
90
FWH-90B
90
FWH-80B
80
FWH-100B
100
FWH-125B
125
FWH-175B
175
FWH-200B
200
FWH-200B
200
SIEPCYEUOQ2V01A Q2V Technical Manual

Advertisement

Table of Contents
loading

Table of Contents