Omron Q2V Series Technical Manual page 164

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

5.2 European Standards
A - Grounding surface (Remove any
paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
5.
Connect the DC reactor to decrease harmonic distortion.
Refer to
DC Reactor Selection on page 165
Note:
• To maintain compliance with EN 61000-3-2 on drive models 2001 to 2006, 4001 to 4004, install a DC reactor.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
External EMC Noise Filter Selection
Drive model
2001
2002
2004
2006
2010
2012
2021
2030
2042
164
Figure 5.13 EMC Noise Filter and Drive Installation Procedure
Table 5.10 External EMC Noise Filter (2xxxA)
EMC Noise Filter Model
FS23637-8-07
FS23637-8-07
FS23637-8-07
FS23637-8-07
FS23637-14-07
FS23637-14-07
FS23637-24-07
*1
FS5973-35-07
*1
FS5973-60-07
F - Motor
G - Motor cable (Braided shield
cable: 10 m (32.8 ft) maximum)
H - Cable clamp
I - Grounding wire
J - EMC noise filter
to select a DC reactor.
Quantity
1
1
1
1
1
1
1
1
1
Manufacturer
Schaffner
Schaffner
Schaffner
Schaffner
Schaffner
Schaffner
Schaffner
Schaffner
Schaffner
SIEPCYEUOQ2V01A Q2V Technical Manual

Advertisement

Table of Contents
loading