H2-xx: MFDO Function Select
Setting Value
Function
0
Through Mode
1
Drive Ready
2
Drive Enable
3
Fault
4
Alarm
5
@Run
6
@Reverse
7
Zero Speed
B
@FreqOutput
D
LO/RE Status
E
EDM Safety
F
SpeedAgree1
10
USpeedAgree1
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via Modbus or the communication option. This signal does not function if signals from the PLC are not
configured.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive is ready and running.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
This terminal activates when the H1-xx = 1A [Drive Enable] terminal activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal turns on when the drive detects a minor fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the Run command is input and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the output frequency is less than the value of E1-09 [Min Output Frequency] or b2-01
[ZSpd/DCI Threshold].
Note:
Parameter A1-02 [Control Method] selects which parameter is the reference.
A1-02 Setting
Control Method Selection
0
V/f Control
2
OLVector
5
PM OLVector
6
PM AOLVector
8
EZ Vector
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
OFF : REMOTE
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [SpAgree Det.
Width].
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is running.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-01 [SpAgree Det.Level] ± L4-02 [SpAgree
Det.Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is within the range as defined by the result of "L4-01 ± L4-02" and the range of
frequency reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" nor the range of frequency reference ± L4-02.
Description
Parameter Used as the Reference
E1-09
b2-01
E1-09
E1-09
E1-09
11.9 H: TERMINALS
Ref.
595
595
595
595
596
596
596
596
597
597
598
598
598
355