11.7 E: MOTOR
No.
Name
(Hex.)
E1-12
Min Output Voltage
(030B)
Expert
E1-13
Base Voltage
(030C)
Expert

E2: MOTOR 1 PARAMETERS

No.
Name
(Hex.)
E2-01
Mot Rated Current
(FLA)
(030E)
E2-02
Mot Rated Slip
(030F)
E2-03
Mot No-Load Current
(0310)
E2-04
Motor Pole Count
(0311)
E2-05
Motor L-L Resistance
(0312)
E2-06
Motor Leak Inductance
(0313)
E2-07
Mot Sat Coeff 1
(0314)
E2-08
Mot Sat Coeff 2
(0315)
E2-09
Motor Mech Loss
(0316)
Expert
E2-10
Motor Iron Loss
(0317)
E2-11
Motor Rated Power
(kW)
(0318)

E3: V/F PARAMETER MOTOR 2

No.
Name
(Hex.)
E3-01
M2 Control Method
Selection
(0319)
E3-04
M2 Max Out Frequency
(031A)
E3-05
M2 Max Out Voltage
(031B)
336
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets a middle point voltage for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the base voltage for the V/f pattern.
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor rated current in amps.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets motor rated slip.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the no-load current for the motor in amps when operating at the rated frequency
and the no-load voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of motor poles.
Note:
• When A1-02 = 0 [Control Method = V/f Control], the maximum value is 120.
• When A1-02 = 2 [OLVector], the maximum value is 48.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the line-to-line resistance for the motor stator windings.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the voltage drop from motor leakage inductance when the motor is operating at the
rated frequency and rated current. This value is a percentage of Motor Rated Voltage.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the mechanical loss of the motor. It is set as a percentage of E2-11 [Motor Rated
Power (kW)]. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor iron loss.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated output in the units from o1-58 [Mot Capacity Unit].
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the control method for motor 2.
Note:
When you change this setting, the drive will set all parameters that are dependent on
this parameter to their default settings.
0 : V/f Control
2 : OLVector
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set the maximum output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the maximum output voltage for the motor 2 V/f pattern.
Default
(Range)
0.0 V
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 -
510.0 V)
Default
(Range)
Determined by o2-04,
C6-01
(10% to 200% of the
drive rated current)
Determined by o2-04,
C6-01
(0.000 - 20.000 Hz)
Determined by o2-04,
C6-01
(0 to E2-01)
4
(2 - 120)
Determined by o2-04,
C6-01
(0.000 - 65.000 Ω)
Determined by o2-04,
C6-01
(0.0 - 60.0%)
0.50
(0.00 - 0.50)
0.75
(E2-07 - 0.75)
0.0%
(0.0 - 10.0%)
Determined by o2-04,
C6-01
(0 - 65535 W)
Determined by o2-04,
C6-01
(0.00 - 650.00 kW)
Default
(Range)
0
(0, 2)
Determined by E3-01
(40.0 - 590.0 Hz)
Determined by E3-01
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)