7.10 Troubleshooting Without Fault Display
The Drive Frequency Reference Is Different than the Controller Frequency
Reference Command
Causes
The analog input gain and bias for the frequency reference input are set
incorrectly.
The drive is receiving frequency bias signals from analog input terminals
AI1 and AI2 and the sum of all signals makes the frequency reference.
PID control is enabled.

The Motor Speed Is Not Stable When Using a PM Motor

Causes
E5-01 [PM Mot Code Selection] is set incorrectly.
The drive is operating the motor at more than the specified speed control
range.
The motor is hunting.
Hunting occurs at start.
Too much current is flowing through the drive.
Operation is not stable when n8-57 = 1 [High-Freq Injection = Enabled].

There Is Too Much Motor Oscillation and the Rotation Is Irregular

Causes
Unsatisfactory balance of motor phases.
The motor is hunting.

Deceleration Takes Longer Than Expected When Dynamic Braking Is Enabled

Causes
The stall prevention during deceleration setting is incorrect.
The deceleration time setting is too long.
The motor torque is not sufficient.
262
Possible Solutions
Examine the gain and bias settings for the analog inputs that set the frequency reference.
• Terminal AI1: H3-03 [AI1 Gain Setting], H3-04 [AI1 Bias Setting]
• Terminal AI2: H3-11 [AI2 Gain Setting], H3-12 [AI2 Bias Setting]
• Examine parameters H3-02, H3-10 [MFAI Function Select]. If both of these parameters = 4
[Freq Ref/BIAS], change the settings.
• Use U1-13, U1-14 [Terminal AI1 InputLv, Terminal AI2 InputLv] to make sure that the analog
input values set to terminals AI1 and AI2 are applicable.
If PID control is not necessary, set b5-01 = 0 [PID Enable = Disabled].
Note:
When PID control is enabled, the drive adjusts the output frequency as specified by the target
value. The drive will only accelerate to the maximum output frequency set in E1-04 [Max
Output Frequency] while PID control is active.
Possible Solutions
Refer to "Motor Performance Fine-Tuning" in the technical manual.
Examine the speed control range and adjust the speed.
Adjust these parameters to have the largest effect:
• n8-55 [Load Inertia]
• n8-45 [SpdFbck Det.Gain]
• C4-02 [Trq Comp Delay Time]
Increase the value set in C2-01 [Jerk@Start of Accel].
Set E5-01 [PM Mot Code Selection] correctly as specified by the motor. For special-purpose
motors, enter the correct value to E5-xx as specified by the motor test report.
• Do High Frequency Injection Auto-Tuning.
• Decrease the value set in n8-41 [HFI PoleDet Pgain] in increments of 0.5.
Note:
Set n8-41 > 0.0 for IPM motors.
Possible Solutions
• Make sure that the drive input power voltage supplies stable power.
• Set L8-05 = 0 [In PhaseLoss Selection = Disabled].
• Set n1-01 = 1 [HuntPrev Selection = Enabled].
• Increase the value of n2-01 [AFR Gain] or n2-02 [AFR Time 1].
Possible Solutions
• Examine the setting for L3-04 [StallP@Decel Enable].
• When the drive has a dynamic braking option installed, set L3-04 = 0 [Disabled].
• If the drive detects ov [Overvoltage], set L3-04 = 1 [Enabled] and L3-50 = 2 [StallP@Decel
Mode = Gen Purpose w/ DB Resistor].
Set C1-02, C1-04, C1-06, or C1-08 [Deceleration Times] to applicable values.
Use a larger motor.
Note:
If these items are correct, the demand on the motor is more than the motor capacity:
• Parameter settings are correct.
• The drive does not detect ov [Overvoltage].
SIEPCYEUOQ2V01A Q2V Technical Manual