Communications Data Table - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

6.3 Modbus Communications
4.
Connect a jumper between control circuit terminals DI6 and D0V.
5.
Energize the drive.
6.
When normal, the keypad will show PASS [Modbus Communications Test Mode Normal].
When there is an error, the keypad will show CE [Modbus Communications Error].
7.
De-energize the drive.
8.
Disconnect the wire jumper between terminals DI6 and D0V. Set terminal DI6 to its initial function.
Self-Diagnostics is complete and the drive returns to its usual function.

Communications Data Table

The communication data types are command data, monitor data, and broadcast message.
Command Data
You can read and write command data.
Note:
Set the reserved bit to 0. Do not write the data in the reserved register or the monitor register.
200
Figure 6.12 Self-Diagnostics Jumper Terminals
SIEPCYEUOQ2V01A Q2V Technical Manual