12.2 b: APPLICATION
Note:
• Set b5-01 = 1 to enable this parameter.
• When b5-61 = 1, you can use this formula to adjust PID output proportional to the frequency reference:
U5-03 [PID Output], Fref [Frequency Reference], and Fmax [Maximum Output Frequency]
*1
Lower limit = b5-62, Upper limit = Maximum output frequency
b5-62: PID LoLim Value for Trim Mode
No.
Name
(Hex.)
b5-62
PID LoLim Value for Trim
Mode
(119B)
Note:
Set b5-01 = 1 to enable this parameter.
b5-63: PID DifFB Mon Selection
No.
Name
(Hex.)
b5-63
PID DifFB Mon Selection
(119C)
Note:
• You cannot select parameter U5-xx.
• This parameter is disabled when set to 000.
b5-64: PID DifFB Mon Gain
No.
Name
(Hex.)
b5-64
PID DifFB Mon Gain
(119D)
b5-65: PID DifFB Mon Bias
No.
Name
(Hex.)
b5-65
PID DifFB Mon Bias
(119F)
b5-66: PID Fback Mon Level
No.
Name
(Hex.)
b5-66
PID Fback Mon Level
(11DE)
0 : Absolute
1 : Bi-directional (+/-)
b5-67: PID DifFB Mon Level
No.
Name
(Hex.)
b5-67
PID DifFB Mon Level
(11DF)
0 : Absolute
1 : Bi-directional (+/-)
480
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PID Trim Mode Lower Limit Value as a percentage of the maximum output frequency.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of the Ux-xx
[Monitor].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for the monitor specified in b5-63 [PID DifFB Mon Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias for the monitor specified in b5-63 [PID DifFB Mon Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the signal level for the monitor specified in b5-55 [PID Fback Mon Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the signal level for the monitor specified in b5-63 [PID DifFB Mon Selection].
Description
Description
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
0.00%
(0.00 - 100.00%)
Default
(Range)
000
(000 - 999)
Default
(Range)
1.00
(0.00 - 10.00)
Default
(Range)
0.00
(-10.00 - +10.00)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)