E1-08: Mid A Voltage
No.
Name
(Hex.)
E1-08
Mid A Voltage
(0307)
Note:
Default setting is determined by A1-02 [Control Method], C6-01 [ND/HD Duty Selection], and o2-04 [Drive KVA Selection].
E1-09: Min Output Frequency
No.
Name
(Hex.)
E1-09
Min Output Frequency
(0308)
E1-10: Min Output Voltage
No.
Name
(Hex.)
E1-10
Min Output Voltage
(0309)
E1-11: Mid B Frequency
No.
Name
(Hex.)
E1-11
Mid B Frequency
(030A)
Expert
Note:
Set this parameter to 0.0 to disable the function.
E1-12: Min Output Voltage
No.
Name
(Hex.)
E1-12
Min Output Voltage
(030B)
Expert
Note:
Set this parameter to 0.0 to disable the function.
E1-13: Base Voltage
No.
Name
(Hex.)
E1-13
Base Voltage
(030C)
Expert
Note:
• After Auto-Tuning, the value of E1-13 = E1-05 [Max Output Voltage].
• When E1-13 = 0.0, use the value of E1-05 to control the voltage.

E2: MOTOR 1 PARAMETERS

E2 parameters are used to set induction motor data. To switch drive operation from one motor to another motor,
configure the first motor (motor 1).
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output voltage for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum output frequency for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum output voltage for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets a middle output frequency for the V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle point voltage for the V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the base voltage for the V/f pattern.
Description
Description
Description
Description
Description
Description
12.5 E: MOTOR
Default
(Range)
Determined by A1-02,C6-
01 and o2-04
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by A1-02 and
E5-01
(Determined by A1-02, E1-
04, and E5-01)
Default
(Range)
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
Default
(Range)
0.0 Hz
(0.0 - E1-04)
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
Default
(Range)
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)