Set The Output Signal For The Mfao Terminal Ao; Switch On Termination Resistor For Modbus Communications - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Set the Output Signal for the MFAO Terminal AO

Set the signal type for terminal AO to voltage or current output. Use jumper S5 and H4-07 [AO Signal Level
Select] to set the signal type.
Types of Output Signals
Voltage output
(Default)
Current output

Switch ON Termination Resistor for Modbus Communications

When the drive is the last slave in a Modbus communications, set DIP switch S2 to the ON position. This drive
has a built-in termination resistor for the RS-485 interface.
DIP Switch S2
OFF (Default)
SIEPCYEUOQ2V01A Q2V Technical Manual
Figure 3.31 Location of Jumper Switch S5
Table 3.18 MFAO Terminal AO Signal Settings
Jumper S5
Figure 3.32 Location of DIP Switch S2
Table 3.19 Modbus Communications Termination Resistor Setting
ON
Parameter
Signal Level
H4-07 = 0: 0 V to 10 V
H4-07 = 2: 4 mA to 20 mA
Description
The built-in termination resistor is ON.
The built-in termination resistor is OFF.
3.6 Control I/O Connections
3
83

Advertisement

Table of Contents
loading

Table of Contents