Omron Q2V Series Technical Manual page 707

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

o4-02: Cum.Oper TimeSelect
No.
Name
(Hex.)
Cum.Oper TimeSelect
o4-02
(050C)
1 : Log Power-On Time
Counts the time from when the drive is energized to when it is de-energized.
2 : Log Run Time
Counts the time that the drive outputs voltage.
o4-03: Fan.Oper Setting
No.
Name
(Hex.)
Fan.Oper Setting
o4-03
(050E)
Use monitor U4-03 [Fan Oper.Time] to view the total operation time of the cooling fan. When you replace a
cooling fan, set o4-03 = 0 to reset U4-03. Select o4-03 on the keypad to show the current value of U4-03 in 10-
hour (h) units. If you use the monitor to change o4-03, the recount of U4-03 starts with the o4-03 setting.
The drive sets o4-03 in 10-hour (h) units. When o4-03 = 30, U4-03 [Fan Oper.Time] will show "300 h".
o4-05: Cap.Maint.Setting
No.
Name
(Hex.)
Cap.Maint.Setting
o4-05
(051D)
When you replace a drive, set o4-05 = 0 to reset U4-05. When the o4-05 setting changes, the count of U4-05
starts again as specified by the setting of o4-05. After you complete the configuration, o4-05 automatically resets
to 0.
Note:
The maintenance period changes for different operating environments.
o4-07: PreChgRly Preset Maintenance Cnt
No.
Name
(Hex.)
PreChgRly Preset
o4-07
Maintenance Cnt
(0523)
When you replace a drive, set o4-07 = 0 to reset U4-06. When the o4-07 setting changes, the count of U4-06
starts again as specified by the setting of o4-07. After you complete the configuration, o4-07 automatically resets
to 0.
Note:
The maintenance period changes for different operating environments.
o4-09: IGBT Preset Maintenance Cnt
No.
Name
(Hex.)
IGBT Preset Maintenance
o4-09
Cnt
(0525)
When you replace a drive, set o4-09 = 0 to reset U4-07. When the o4-09 setting changes, the count of U4-07
starts again as specified by the setting of o4-09. After you complete the configuration, o4-09 automatically resets
to 0.
Note:
The maintenance period changes for different operating environments.
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the condition that counts the cumulative operation time.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour
units.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the U4-05 [Capacitor Maintenance] monitor value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the U4-06 [SoftChgRelay Maint] monitor value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the U4-07 [IGBT Maintenance] monitor value.
Description
Description
Description
Description
Description
12.10 o: KEYPAD
Default
(Range)
1
(1, 2)
Default
(Range)
0 h
(0 - 9999 h)
Default
(Range)
0%
(0 - 150%)
Default
(Range)
0%
(0 - 150%)
Default
(Range)
0%
(0 - 150%)
12
707