4.4
Drive Mode and Programming Mode
The keypad display of this drive has two modes: Drive Mode and Programming Mode.
• Drive Mode
Use this mode to operate the drive. These operations are available:
– Monitor operation statuses (for example, output frequency, output current, and output voltage)
– Set parameters that you can set while the drive is operating (for example, d1-01 to d1-17). Refer to
Details on page
431 for more information.
• Programming Mode
Use this mode to set parameters. These operations are available:
– Examine and set the parameters that are not at default settings (Verify Mode)
– See and set all parameters (Parameter Setting Mode)
– Automatically set motor parameters (Auto-Tuning Mode)
The following tables give information about the functions you can access when you push
Note:
You can use b1-08 [RUN@PRG Mode Selection] to set the drive to accept Run commands from an external source while in
Programming Mode.
• Set b1-08 = 1 [NoRUN@Program] to reject the Run command from an external source while in Programming Mode.
• Set b1-08 = 2 [RUN@Program] to accept the Run command from an external source while in Programming Mode.
• Set b1-08 = 3 [Program@Stop only] to prevent changes from Drive Mode to Programming Mode.
◆
Drive Mode (Operation of the motor and monitoring of operation status)
Description
LED Display
Frequency
reference display
Monitor display
Output voltage
display
Output current
display
Output frequency
indicator
Forward/reverse
selection
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 4.3 Overview of the Modes
You can set and monitor frequency references.
Note:
You can change what is shown on the keypad when you energize the drive. Use o1-02 [Monitor Selection at
Power-up] to set the items. When A1-02 = 6 [Control Method = PM AOLVector], the display unit is %.
The keypad shows Ux-xx [Monitor].
You can monitor the output voltage reference.
Use o1-01 [User Monitor Selection] to change the items shown on this display.
You can monitor the output current.
You can monitor the frequency output from the drive.
: Motor rotates in forward direction
: Motor rotates in reverse direction
Note:
For applications where the motor must not rotate in reverse direction (for example, for fans and pumps), you can
use b1-04 [Reverse Operation Selection] to prevent reverse rotation.
How to set reverse operation
4.4 Drive Mode and Programming Mode
Description
Parameter
/
.
Ref.
-
-
313
-
4
-
-
109