Drive Mode And Programming Mode - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

4.4

Drive Mode and Programming Mode

The keypad display of this drive has two modes: Drive Mode and Programming Mode.
• Drive Mode
Use this mode to operate the drive. These operations are available:
– Monitor operation statuses (for example, output frequency, output current, and output voltage)
– Set parameters that you can set while the drive is operating (for example, d1-01 to d1-17). Refer to
Details on page
431 for more information.
• Programming Mode
Use this mode to set parameters. These operations are available:
– Examine and set the parameters that are not at default settings (Verify Mode)
– See and set all parameters (Parameter Setting Mode)
– Automatically set motor parameters (Auto-Tuning Mode)
The following tables give information about the functions you can access when you push
Note:
You can use b1-08 [RUN@PRG Mode Selection] to set the drive to accept Run commands from an external source while in
Programming Mode.
• Set b1-08 = 1 [NoRUN@Program] to reject the Run command from an external source while in Programming Mode.
• Set b1-08 = 2 [RUN@Program] to accept the Run command from an external source while in Programming Mode.
• Set b1-08 = 3 [Program@Stop only] to prevent changes from Drive Mode to Programming Mode.
Drive Mode (Operation of the motor and monitoring of operation status)
Description
LED Display
Frequency
reference display
Monitor display
Output voltage
display
Output current
display
Output frequency
indicator
Forward/reverse
selection
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 4.3 Overview of the Modes
You can set and monitor frequency references.
Note:
You can change what is shown on the keypad when you energize the drive. Use o1-02 [Monitor Selection at
Power-up] to set the items. When A1-02 = 6 [Control Method = PM AOLVector], the display unit is %.
The keypad shows Ux-xx [Monitor].
You can monitor the output voltage reference.
Use o1-01 [User Monitor Selection] to change the items shown on this display.
You can monitor the output current.
You can monitor the frequency output from the drive.
: Motor rotates in forward direction
: Motor rotates in reverse direction
Note:
For applications where the motor must not rotate in reverse direction (for example, for fans and pumps), you can
use b1-04 [Reverse Operation Selection] to prevent reverse rotation.
How to set reverse operation

4.4 Drive Mode and Programming Mode

Description
Parameter
/
.
Ref.
-
-
313
-
4
-
-
109

Advertisement

Table of Contents
loading

Table of Contents