Omron Q2V Series Technical Manual page 628

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

12.7 H: TERMINALS
WARNING! Sudden Movement Hazard. Before you do a test run, make sure that the setting values for virtual input and output
function parameters are correct. Virtual input and output functions can have different default settings and operation than wired
input and output functions. Incorrect function settings can cause serious injury or death.
[Virtual Multi-Function
Note:
• Refer to
H1: DIGITAL INPUTS on page 566
• Refer to
H2: DIGITAL OUTPUTS on page 587
• Refer to
H3: ANALOG INPUTS on page 608
• Refer to
H4: ANALOG OUTPUTS on page 618
• You cannot set 5 [3-Wire Seq.] and 20 to 2F [External Fault] to H7-01 to H7-04 [Virtual In1 Select Function to Virtual In4 Select
Function].
• If the terminal is not used, set H7-01 to H7-04 = 0. However, the through mode function is not supported.
H7-00: Virtual MFIO Selection
No.
Name
(Hex.)
H7-00
Virtual MFIO Selection
(116F)
Expert
0 : Disabled
1 : Enabled
H7-01: Virtual In1 Select Function
No.
Name
(Hex.)
H7-01
Virtual In1 Select Function
(1185)
Expert
H7-02: Virtual In2 Select Function
No.
Name
(Hex.)
H7-02
Virtual In2 Select Function
(1186)
Expert
H7-03: Virtual In3 Select Function
No.
Name
(Hex.)
H7-03
Virtual In3 Select Function
(1187)
Expert
628
Figure 12.104 Virtual Analog I/O Functional Block Diagram
H7-10
Output 1]
Figure 12.105 Virtual Digital I/O Functional Block Diagram
for more information on the virtual digital input setting values.
for more information on the virtual digital output setting values.
for more information on the virtual analog input setting values.
for more information on the virtual analog output setting values.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate
the virtual I/O function.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that enters the virtual input set in H7-10 [Virtual Out1 Select Function].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that enters the virtual input set in H7-12 [Virtual Out2 Select Function].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that enters the virtual input set in H7-14 [Virtual Out3 Select Function].
H7-11
[Virtual Output
1 Delay Time]
Description
Description
Description
Description
H7-01
[Virtual Multi-Function
Input 1]
(0 - 4, 6 - 19F)
(0 - 4, 6 - 19F)
(0 - 4, 6 - 19F)
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
0
(0, 1)
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0

Advertisement