Omron Q2V Series Technical Manual page 171

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Single-Phase 200 V Class (UL Compliance)
Model
Terminal
L/L1, N/L2
U/T1, V/T2, W/T3
B001
-, +1
B1, B2
L/L1, N/L2
U/T1, V/T2, W/T3
B002
-, +1
B1, B2
L/L1, N/L2
U/T1, V/T2, W/T3
B004
-, +1
B1, B2
L/L1, N/L2
U/T1, V/T2, W/T3
B006
-, +1
B1, B2
L/L1, N/L2
U/T1, V/T2, W/T3
B010
-, +1
B1, B2
SIEPCYEUOQ2V01A Q2V Technical Manual
Recommended
Applicable Gauge
Gauge
AWG, kcmil
AWG, kcmil
14
14
14
14
14
14
14
14
*2
*2
14
14
14
14
14
14
14
14
14
14
*2
*2
14
14
14
14
14
14
14
14
14
14
*2
*2
14
14
12
14 - 10
14
14 - 12
12
14 - 10
14
14 - 12
*2
*2
10
14 - 10
10
12 - 10
14
14 - 12
10
12 - 10
14
14 - 12
*2
*2
10
14 - 10
Wire
Terminal Screw
Stripping
*1
Length
Size
Shape
mm
6.5
M3
6.5
M3
6.5
M3
6.5
M3
-
M3.5
6.5
M3
6.5
M3
6.5
M3
6.5
M3
-
M3.5
6.5
M3
6.5
M3
6.5
M3
6.5
M3
-
M3.5
8
M3
8
M3
8
M3
8
M3
-
M4
8
M3
8
M3
8
M3
8
M3
-
M4
5.3 UL Standards
2
(copper wire).
Tightening Torque
N∙m (in∙lb)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.8 - 1.0
(7.1 - 8.9)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.8 - 1.0
(7.1 - 8.9)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.8 - 1.0
(7.1 - 8.9)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
5
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
1.2 - 1.5
(10.6 - 13.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
0.5 - 0.6
(4.4 - 5.3)
1.2 - 1.5
(10.6 - 13.3)
171