Omron Q2V Series Technical Manual page 350

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

11.9 H: TERMINALS
Setting Value
Function
11
LOC/REM Sel.
12
AI Input Sel
15
FWD/REV Det
16
Ref Sample
17
Ac/Dec Hold
18
Ac/Dec Time1
19
Ac/Dec Time2
1A
Drive Enable
1B
Baseblock NO
1E
Baseblock NC
20 to 2F
External Fault
30
DCInj Cmd
32
HiSlipBraking
34
Fast Stop NO
35
Fast Stop NC
350
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : LOCAL
OFF : REMOTE
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command that enables or disables the terminals selected in H3-14 [An.In Term.Enable Sel].
ON : Input to the terminal selected with H3-14 is enabled
OFF : Input to the terminal selected with H3-14 is disabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to sample the frequency reference at terminal AI1 or AI2, and hold the frequency reference at
that frequency.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output
frequency that was stored in the drive at the time of the pause, and restarts motor operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-
03, C1-04].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set this function and H1-xx = 18 [Ac/Dec Time1] together. Sets the drive to use Acceleration/Deceleration Time 3
[C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is
OFF.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (ExF NO-AlRmp)
21 : External Fault (ExF NC-AlRmp)
22 : External Fault (ExF NO-RnRmp)
23 : External Fault (ExF NC-RnRmp)
24 : External Fault (ExF NO-AlCoast)
25 : External Fault ExF NC-AlCoast)
26 : External Fault (ExF NO-RnCoast)
27 : External Fault (ExF NC-RnCoast)
28 : External Fault (ExF NO-AlFStop)
29 : External Fault (ExF NC-AlFStop)
2A : External Fault (ExF NO-RnFStop)
2B : External Fault (ExF NC-RnFStop)
2C : External Fault (ExF NO-AlAlarm)
2D : External Fault (ExF NC-AlAlarm)
2E : External Fault (ExF NO-RnAlarm)
2F : External Fault (ExF NC-RnAlarm)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method = EZ Vector], this function is available only when you use a PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to use high-slip braking to stop the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
Description
SIEPCYEUOQ2V01A Q2V Technical Manual