At this point the inverter is ready to run the motor for the first time, but first review this check-list:
Verify the power LED is ON. If not, check the power connections.
Verify the PRG LED is OFF. If it is ON, review the instructions above.
Make sure the motor is disconnected from any mechanical load.
Make sure that you have a frequency reference checking the content of F001 and the Hz Led on operator
Now give the RUN command from the selected source. The RUN LED will turn ON.
The motor should start turning.
Remove the RUN command or press the STOP key to stop the motor rotation.

3.6 Auto tuning (SLV Mode)

The MX2 inverter has auto-tuning function to get suitable motor control performance by measuring the motor constants auto-
matically. Auto-tuning is effective only for sensorless vector control. Basically two modes are available the static and the rotative
one:
Static is less accurate but it could be used in situations where motor rotation could damage the mechanics. For this mode nei-
ther the I0 (no-load current) or the J (inertia) are calculated.
Rotative auto-tuning moves the motor following a special operation pattern to find the motor characteristics. However, the
torque during auto-tuning is not sufficient so is recommended to detach the mechanical system and don't use for example
with vertical loads.
The Auto-tuning mode is selected by parameter H001 and after it finish succefully is necessary to to select the auto-tuning
parameters by parameter H002.
Parameter
For a correct auto-tuning calculation please take into account following recommendations before starting:
Use only a motor of the same size or one size lower than the inverter.
Be sure to disable the DC braking setting (A051=00)
Be sure to deactivate ATR digital input (52: Enable torque cmd. input)
Motor rotates up to 80% of base frequency, check if it's a problem for the application.
Motor should not be driven by any other external force.
All the brakes should be released
Be sure that physical limtis of the machine will not be reach
Even for none-rotative auto-tuning there is a risk that motor moves slightly
After checking the above points and setting parameter H001 procced with the activation of the Run command from the source
selected on A002 and the auto-tuning will start. Please check the diagram on next page for detailed information of all the steps.
After the tuning the H001 returns to "00" status and the motor characteristics are transferred to those parameter, remember to
set H002 to use them.
Parameter
Note: In case rotary tuning is not possible or autotuning results in very high No Load current (H033) (this is possible with small
motors), please use this formula to calculate theoretical value:
H033 = Inom * sin (arccos(cos phi)).
18
Parameter Name
H001
Auto-tuning selection
H002
Motor constant selection
Parameter Name
H030
Motor constant R1
H031
Motor constant R2
H032
Motor constant L
H033
Motor constant I0
H034
Motor constant J
Description
00: Disable
01: Enabled with motor stop
02: Enabled with motor rotation
00: Standard motor
02: Auto tuned data
Description
0.001 to 65.535 Ohms
0.001 to 65.535 Ohms
0.01 to 655.35 mH
0.01 to 655.35 A
0.001 to 9999 kgm2