12.5 E: MOTOR
HD : 2001 - 2021, B001 - B018, 4001 - 4012
ND : 2001 - 2018, B001 - B012, 4001 - 4009
E : HF_60-180Hzmax
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate
at more than 60 Hz.
Note:
The voltage values in the figures are for 200 V class drives. Multiply the values by 2 for 400 V class drives.
HD : 2001 - 2021, B001 - B018, 4001 - 4012
ND : 2001 - 2018, B001 - B012, 4001 - 4009
F : Custom
Set E1-04 to E1-13 [V/f Pattern for Motor 1] to set the values for this custom pattern.
The default settings are the same as Setting Value 0 [CT_50-50Hzmax].
E1-04: Max Output Frequency
No.
Name
(Hex.)
E1-04
Max Output Frequency
(0303)
E1-05: Max Output Voltage
No.
Name
(Hex.)
E1-05
Max Output Voltage
(0304)
E1-06: Base Frequency
No.
Name
(Hex.)
E1-06
Base Frequency
(0305)
E1-07: Mid A Frequency
No.
Name
(Hex.)
E1-07
Mid A Frequency
(0306)
530
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the maximum output frequency for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the maximum output voltage for the V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the base frequency for the V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output frequency for the V/f pattern.
HD : 2030 - 2082, 4018 - 4060
ND : 2021 - 2082, 4012 - 4060
HD : 2030 - 2082, 4018 - 4060
ND : 2021 - 2082, 4012 - 4060
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
Determined by A1-02 and
E5-01
(Determined by A1-02 and
E5-01)
Default
(Range)
200.0
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by A1-02 and
E5-01
(0.0 - E1-04)
Default
(Range)
Determined by A1-02
(0.0 - E1-04)