Omron Q2V Series Technical Manual page 393

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

No.
Name
(Hex.)
U1-11
Out Terminal Status
(004A)
U1-12
Drive Status
(004B)
U1-13
Terminal AI1 InputLv
(004E)
U1-14
Terminal AI2 InputLv
(004F)
U1-16
SFS Output Frequency
(0053)
U1-18
oPE Fault Parameter
(0061)
U1-19
Modbus Err.Code
(0066)
U1-24
Input Pulse Monitor
(007D)
U1-25
SoftNumber Flash
(004D)
U1-26
SoftNumber ROM
(005B)
U1-50
Virt. Analog Input
(1199)
Expert
U1-91
Output Voltage
(154E)
Expert
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminal where
For example, U1-11 shows
when terminals NO and DO2 are ON.
bit0 : Terminal NO/NC-CM
bit1 : Terminal DO1-O1C
bit2 : Terminal DO2-O2C
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows drive status where
= ON and
For example, U1-12 shows
during run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the signal level of terminal AI1.
Unit: 0.1%
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the signal level of terminal AI2.
Unit: 0.1%
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the output frequency after soft start. Shows the frequency with acceleration and
deceleration times and S-curves. Parameter o1-03 [FrqDisplay Unit Selection] sets the display
units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08
[Parameter Selection Error].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the contents of the Modbus communication error where
For example, U1-19 shows
when the drive detects a CRC error.
bit0 : CRC Error
bit1 : Data Length Error
bit2 : Not used (normal value of [ ]).
bit3 : Parity Error
bit4 : Overrun Error
bit5 : Framing Error
bit6 : Timed Out
bit7 : Not used (normal value of [ ]).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the frequency to pulse train input terminal PI.
Unit: 1 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the ID.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the ROM ID.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the virtual analog input value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the drive internal output voltage reference.
Unit: 0.1 V
Description
= (ON) and
= (OFF).
= OFF.
= "no error".
="error" and
11.16 U: MONITORS
MFAO Signal Level
No signal output available
No signal output available
10 V = 100% (-10 V to +10
V)
10 V = 100% (-10 V to +10
V)
10 V = Maximum
frequency (-10 V to +10 V)
No signal output available
No signal output available
Determined by H6-02
No signal output available
No signal output available
Determined by H7-40
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
393