Omron Q2V Series Technical Manual page 712

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

12.10 o: KEYPAD
Stops the data log.
1 : ON (Data Logging)
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sample Lapse].
o5-02: Log Sample Lapse
No.
Name
(Hex.)
Log Sample Lapse
o5-02
(1552)
RUN
o5-03: Log Mon Data 1
No.
Name
(Hex.)
Log Mon Data 1
o5-03
(1553)
RUN
Note:
Set the number of the U monitor to record the data log.
For example, to show U1-01 [PID Feedback], set o5-03 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot set [U2: FAULT] or [U3: FAULT HISTORY].
o5-04: Log Mon Data 2
No.
Name
(Hex.)
Log Mon Data 2
o5-04
(1554)
RUN
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
o5-05: Log Mon Data 3
No.
Name
(Hex.)
Log Mon Data 3
o5-05
(1555)
RUN
Note:
Sets the number of the U monitor you will log.
For example, to show U1-03 [Output Current], set o5-05 = 103. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select [U2: FAULT] or [U3: FAULT HISTORY].
o5-06: Log Mon Data 4
No.
Name
(Hex.)
Log Mon Data 4
o5-06
(1556)
RUN
Note:
Sets the number of the U monitor you will log.
For example, to show U1-07 [DC Bus Voltage], set o5-06 = 107. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select [U2: FAULT] or [U3: FAULT HISTORY].
712
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the data log monitor. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the data log monitor. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data log monitor. This parameter is only available when using an LCD keypad.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Description
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
1000 ms
(100 - 60000 ms)
Default
(Range)
101
(000, 101 - 999)
Default
(Range)
102
(000, 101 - 999)
Default
(Range)
103
(000, 101 - 999)
Default
(Range)
107
(000, 101 - 999)

Advertisement