12.7 H: TERMINALS
Note:
• Set A1-02 = 0 and H6-01 = 3 to show C5 parameters.
• You cannot use Closed Loop V/f Control mode with the Motor Switch function.
H6-02: PI Frequency Scale
No.
Name
(Hex.)
H6-02
PI Frequency Scale
(042D)
RUN
H6-03: PI Function Gain
No.
Name
(Hex.)
H6-03
PI Function Gain
(042E)
RUN
H6-04: PI Function Bias
No.
Name
(Hex.)
H6-04
PI Function Bias
(042F)
RUN
H6-05: PI Filter Time
No.
Name
(Hex.)
H6-05
PI Filter Time
(0430)
RUN
H6-06: PO Mon.Selection
No.
Name
(Hex.)
H6-06
PO Mon.Selection
(0431)
RUN
Note:
To use in through mode or when terminal PO is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
• Use the pulse train monitor as the sourcing output.
626
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency of the pulse train input signal used when the item selected with H6-01 [PI
Pulse Train Function] is input at 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain used when the function in H6-01 [PI Pulse Train Function] is input to terminal PI.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias used when the function in H6-01 [PI Pulse Train Function] is input to terminal PI.
Sets a value at the time when the pulse train is 0 Hz.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant for the pulse train input primary delay filters.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a function for pulse train monitor output terminal PO. Sets the "x-xx" part of the Ux-xx
monitor.
Output Voltage
VRL(V)
5 V or more
8 V or more
10 V or more
Description
Description
Description
Description
Description
Load Impedance (kΩ)
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
1440 Hz
(100 - 32000 Hz)
Default
(Range)
100.0%
(0.0 - 1000.0%)
Default
(Range)
0.0%
(-100.0 - 100.0%)
Default
(Range)
0.10 s
(0.00 - 2.00 s)
Default
(Range)
102
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
855)