12.4 d: REFERENCE

d6: FIELD WEAKENING / FORCING

d6 parameters set the field weakening and field forcing functions.
The field weakening function decreases the energy consumption of the motor. It decreases the output voltage of
the drive to a set level. The function decreases the motor excitation current inversely proportional to speed in a
constant output range, and does not let the induced voltage of the motor become more than the power supply
voltage. To enable this function, set Field weakening [H1-xx = 44] ON.
Note:
Use the Field Weakening function in constant light-load applications. To control the energy consumption of the motor for other load
conditions, use the parameters b8: ENERGY SAVING.
The Field Forcing function adjusts the delaying influence of the motor time constant when the drive changes the
excitation current reference and it also increases motor responsiveness. This function uses a high motor excitation
current reference for drive start-up only to help develop actual motor excitation current. Enable the Field Forcing
function to increase motor responsiveness.
Note:
You cannot use Field Forcing during DC Injection Braking.
d6-01: Field Weak Level
No.
Name
(Hex.)
d6-01
Field Weak Level
(02A0)
d6-02: Field Weak FqLimit
No.
Name
(Hex.)
d6-02
Field Weak FqLimit
(02A1)
Make sure that these two conditions are correct to enable the Field Weakening command:
• The output frequency ≥ d6-02.
• There is a speed agreement status.
d6-03: Field Force Selection
No.
Name
(Hex.)
d6-03
Field Force Selection
(02A2)
0 : Disabled
1 : Enabled
d6-06: Field Force Limit
No.
Name
(Hex.)
d6-06
Field Force Limit
(02A5)
Note:
You cannot use Field Forcing during DC Injection Braking.

d7: OFFSET FREQUENCY

The drive will use 3 digital signal inputs, to add or subtract the set frequency (Offset frequency) to/from the
frequency reference and correct the speed. The drive uses the terminal set in H1-xx = 0E to 10 [MFDI Function
Select = Offset Frq 1 to Offset Frq 3] to set the Offset frequency. When you close more than one input at the same
time, the drive adds the selected offset values together.
522
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive output voltage as a percentage of E1-05 [Field Force Selection] when H1-xx = 44
[Field weakening] is activated.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum output frequency to start field weakening.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the field forcing function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the limit value for field forcing to increase the motor excitation current reference as a
percentage of E2-03 [Mot No-Load Current]. Usually it is not necessary to change this setting.
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
80%
(0 - 100%)
Default
(Range)
0.0 Hz
(0.0 - 590.0 Hz)
Default
(Range)
0
(0, 1)
Default
(Range)
400%