12.7 H: TERMINALS
Extend MFDO1 to MFDO3 Function Selection
You can set MFDO functions to bit 0 to bit 2 [Mbus MFDO1 to 3] of Modbus register 15E0 (Hex.). Use H2-40 to
H2-42 [Mbus 15E0h b0 Output Function to Mbus 15E0h b2 Output Function] to select the function.
Figure 12.73 Functional Block Diagram of Modbus Multi-function Output
Register No. (Hex.)
15E0
Note:
• Refer to
H2: DIGITAL OUTPUTS on page 587
• When you do not set functions to H2-40 to H2-42, set them to 0.
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, and H2-66 [NO,NC,CM 2nd Function, DO1 2nd Function, and DO2 2nd Function] to set the
function of the output signal for which you will perform logical operations.
Use H2-61, H2-64, and H2-67 [NO,NC,CM Logic Operation, DO1 Logic Operation, and DO2 Logic Operation]
to set the logical operation.
Figure 12.74 Functional Block Diagram of Logical Operation Output for MFDO 1
Logical Operation Selection
H2-61, H2-64, H2-67
1
2
3
4
5
6
7
8
9
Note:
• If you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the
drive will detect oPE33 [Digital Output Selection Error].
• When you do not use H2-60, H2-63, and H2-66, set them to 0. The through mode function is not supported.
588
Table 12.45 Modbus MFDO Registers
bit0
bit1
bit2
for more information about MFDO setting values.
Table 12.46 MFDO Logical Operation Table
Logical Operation Expression
A=B=1
A=1 or B=1
A=0 or B=0
A=B=0
A=B
A != B
AND(A, )
OR(A, )
-
Name
Mbus MFDO 1
Mbus MFDO 2
Mbus MFDO 3
Logical Operation Notation
A=B
On
SIEPCYEUOQ2V01A Q2V Technical Manual