12.7 H: TERMINALS
15: OutFLowLimSel
Setting Value
Function
15
OutFLowLimSel
16: Mot PTC Input
Setting Value
Function
16
Mot PTC Input
• You can use the Positive Temperature Coefficient (PLC) thermistor as an auxiliary or alternative detection
function for oL1 [Motor Overload] problems to help prevent heat damage to motors. If the PTC input signal is
more than the overload alarm level, oH3 [Motor Overheat (PTC Input)] will flash on the keypad.
• If the drive detects oH3, the motor stops with the method set in L1-03. If the drive detects oH4, the motor stops
with the method set in L1-04. If the drive incorrectly detects motor overheating problems, set L1-05.
30: Q2pack AI1
Setting Value
Function
30
Q2pack AI1
31: Q2pack AI2
Setting Value
Function
31
Q2pack AI2

H4: ANALOG OUTPUTS

H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias,
and select output signal levels.
Calibrate Meters Connected to MFAO Terminal AO
Use these parameters to calibrate meters connected to terminal AO:
• H4-02 [AO An.Out Gain]
• H4-03 [AO An.Out Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level.
Use jumper switch S5 and parameter H4-07 [AO Signal Level Select] to set the voltage output and current output.
No.
H4-02
AO An.Out Gain
H4-03
AO An.Out Bias
H4-07
AO Signal Level Select
Figure 12.97
and
Figure 12.98
618
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage of the
current value when the 10 V analog signal is input.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use with Q2pack. Refer to the Q2pack online manual for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use with Q2pack. Refer to the Q2pack online manual for more information.
Name
show the gain and bias.
Description
Description
Description
Description
Range
-999.9 - +999.9%
-999.9 - +999.9%
1: 0 - 10 VDC
3: 4 - 20 mA
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
100.0%
0.0%
1