n8: PM MOTOR CONTROL TUNING

n8 parameters are used to make adjustments when controlling PM motors.
n8-01: PolPos Detection Current
No.
Name
(Hex.)
PolPos Detection Current
n8-01
(0540)
Expert
The drive uses the Initial Rotor Position Estimated Current to detect the initial position of rotors.
Use the "Si" value on the motor nameplate, if available.
n8-02: Pole Align Current Level
No.
Name
(Hex.)
Pole Align Current Level
n8-02
(0541)
Expert
The drive uses the polar pull-in current to attract the rotor after it detects the initial rotor position. When you
increase the value of n8-02, the starting torque also increases.
• If the motor does not track correctly at the time of the polar attraction, increase the value in 10% increments.
• If the motor oscillates at the time of the polar attraction, decrease the value in 10% increments.
n8-11: Observ.Calc Gain2
No.
Name
(Hex.)
Observ.Calc Gain2
n8-11
(054A)
Note:
When n8-72 = 1 [Spd Obs. Method Selection = Method 1], the default value is 50.0. When n8-72 = 2 [Method 2], the default value is
150.0.
n8-14: Polar Comp Gain3
No.
Name
(Hex.)
Polar Comp Gain3
n8-14
(054D)
Expert
n8-15: Polar Comp Gain4
No.
Name
(Hex.)
Polar Comp Gain4
n8-15
(054E)
Expert
n8-21: Mot Back-EMF (Ke) Gain
No.
Name
(Hex.)
Mot Back-EMF (Ke) Gain
n8-21
(0554)
Expert
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets, as a percentage, the Initial Rotor Position Estimated Current, taking the E5-03 [PM Mot
Rated Current (FLA)] as the 100% value. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the current at the time of polar attraction as a percentage where E5-03 [PM Mot Rated
Current (FLA)] is 100%. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Description
Description
Description
Description
Description
Description
12.9 n: SPECIAL
Default
(Range)
50%
(0 - 100%)
Default
(Range)
80%
(0 - 150%)
Default
(Range)
Determined by n8-72
(0.0 - 1000.0)
Default
(Range)
1.000
(0.000 - 10.000)
Default
(Range)
0.500
(0.000 - 10.000)
Default
(Range)
0.90
(0.80 - 1.00)
12