12.7 H: TERMINALS
Apply the primary delay filter to the analog input to enable an analog input signal without the use of high-
frequency noise components. An analog input filter prevents irregular drive control. Drive operation becomes
more stable as the programmed time becomes longer, but it also becomes less responsive to quickly changing
analog signals.
H3-14: An.In Term.Enable Sel
No.
Name
(Hex.)
H3-14
An.In Term.Enable Sel
(041C)
Input signals do not have an effect on terminals not set as targets.
1 : AI1 only
2 : AI2 only
3 : AI1 and AI2
Note:
• The ON/OFF operation of terminal DIx set in AI Input Sel [H1-xx = 12] has an effect on only the analog input terminal selected with
H3-14.
• When H1-xx ≠ 12, the functions set to terminals AI1 and AI2 are always enabled.
H3-16: AI1 Offset
No.
Name
(Hex.)
H3-16
AI1 Offset
(02F0)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input.
H3-17: AI2 Offset
No.
Name
(Hex.)
H3-17
AI2 Offset
(02F1)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA
[H3-09 = 3] is input.
H3-40: 15C1h Input Function
No.
Name
(Hex.)
H3-40
15C1h Input Function
(0B5C)
You can use the MFAI function from Modbus communications. Use this parameter to set the function. Sets the
input for the function in Modbus register 15C1.
Refer to
H3: ANALOG INPUTS on page 608
H3-41: 15C2h Input Function
No.
Name
(Hex.)
H3-41
15C2h Input Function
(0B5F)
You can use the MFAI function from Modbus communications. Use this parameter to set the function. Sets the
input for the function in Modbus register 15C2.
Refer to
H3: ANALOG INPUTS on page 608
612
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the enabled terminal or terminals when H1-xx = 12 [MFDI Function Select = AI Input Sel] is
ON.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the offset level for analog signals input to terminal AI1. Usually it is not necessary to change
this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the offset level for analog signals input to terminal AI2. Usually it is not necessary to change
this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus AI1 function.
for the setting values.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus AI2 function.
for the setting values.
Description
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
3
(1, 2, 3)
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(0, 3, 6 - 2F)
Default
(Range)
0
(0, 3, 6 - 2F)