H2: Digital Outputs - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

H2: DIGITAL OUTPUTS

No.
Name
(Hex.)
H2-01
NO,NC,CM
FuncSelection
(040B)
H2-02
DO1-O1C Func
Selection
(040C)
H2-03
DO2-O2C Func
Selection
(040D)
H2-06
kWH Out Unit Selection
(0437)
H2-07
Mbus Reg1 Address
Select
(0B3A)
H2-08
Mbus Reg1 Bit Select
(0B3B)
H2-09
Mbus Reg2 Address
Select
(0B3C)
H2-10
Mbus Reg2 Bit Select
(0B3D)
H2-20
Compare1 Mon.
Selection
(1540)
H2-21
Compare1 Low Limit
(1541)
H2-22
Compare1 Up Limit
(1542)
H2-23
Compare1 Hysteresis
(1543)
H2-24
Compare1 On-Delay
Time
(1544)
H2-25
Compare1 Off-Delay
Time
(1545)
H2-26
Compare2 Mon.
Selection
(1546)
H2-27
Compare2 Low Limit
(1547)
H2-28
Compare2 Up Limit
(1548)
H2-29
Compare2 Hysteresis
(1549)
H2-30
Compare2 On-Delay
Time
(154A)
H2-31
Compare2 Off-Delay
Time
(154B)
SIEPCYEUOQ2V01A Q2V Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function set for MFDO terminal NO-CM or NC-CM.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDO terminal DO1-O1C.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal DO2-O2C.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the unit for the output signal when H2-01 to H2-03 = 65 [MFDO Function Select
= WattH Pulse].
1 : 0.1 kWh units
2 : 1 kWh units
3 : 10 kWh units
4 : 100 kWh units
5 : 1000 kWh units
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the upper limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output
for the monitor selected in H2-20 [Compare1 Mon.Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the on-delay time for comparator 1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the off-delay time for comparator 1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-26 = 103 to monitor U1-03 [Output Current].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Compare2 Mon.Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the upper limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Compare2 Mon.Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Compare2 Mon.Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the on-delay time for comparator 2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the off-delay time for comparator 2.
11.9 H: TERMINALS
Default
Ref.
(Range)
3
589
(0 - 1FF)
5
589
(0 - 1FF)
F
589
(0 - 1FF)
1
589
(1 - 5)
0001
590
(0001 - 1FFF)
0000
590
(0000 - FFFF)
0001
590
(0001 - 1FFF)
0000
590
(0000 - FFFF)
102
590
(000 - 999)
0.0%
590
(0.0 - 300.0%)
0.0%
590
(0.0 - 300.0%)
0.0%
591
(0.0 - 10.0%)
0.0 s
591
(0.0 - 600.0 s)
0.0 s
591
(0.0 - 600.0 s)
103
591
(000 - 999)
0.0%
591
(0.0 - 300.0%)
0.0%
591
(0.0 - 300.0%)
0.0%
592
(0.0 - 10.0%)
0.0 s
592
(0.0 - 600.0 s)
0.0 s
592
(0.0 - 600.0 s)
353
11