E4: Motor 2 Parameters - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

No.
Name
(Hex.)
E3-06
M2 Base Frequency
(031C)
E3-07
M2 Mid A Frequency
(031D)
E3-08
M2 Mid A Voltage
(031E)
E3-09
M2 Min Out Frequency
(031F)
E3-10
M2 Min Out Voltage
(0320)
E3-11
M2 Mid B Frequency
(0345)
Expert
E3-12
M2 Min Out Voltage
(0346)
Expert
E3-13
M2 Base Voltage
(0347)
Expert

E4: MOTOR 2 PARAMETERS

No.
Name
(Hex.)
E4-01
M2 Rated Current (FLA)
(0321)
E4-02
M2 Rated Slip
(0322)
E4-03
M2 No-Load Current
(0323)
E4-04
M2 Pole Count
(0324)
E4-05
M2 L-L Resistance
(0325)
E4-06
M2 Leak Inductance
(0326)
E4-07
M2 Satur Coeff 1
(0343)
E4-08
M2 Satur Coeff 2
(0344)
E4-09
M2 Mech Loss
(033F)
Expert
E4-10
M2 Iron Loss
(0340)
E4-11
M2 Rated Power (kW)
(0327)
SIEPCYEUOQ2V01A Q2V Technical Manual
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the base frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets a middle output voltage for the motor 2 V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the minimum output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum output voltage for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust
the V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the
V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this
parameter.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated current for motor 2 in amps.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated slip for motor 2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the no-load current for motor 2 in amps when operating at the rated frequency and
the no-load voltage.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the number of poles for motor 2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the line-to-line resistance for the motor 2 stator windings.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated
Voltage when motor 2 operates at the rated frequency and rated current.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [M2 Rated Power
(kW)]. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor iron loss for motor 2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated power in the units from o1-58 [Mot Capacity Unit].
11.7 E: MOTOR
Default
Ref.
(Range)
Determined by E3-01
535
(0.0 - E3-04)
Determined by E3-01
535
(0.0 - E3-04)
Determined by E3-01
535
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
Determined by E3-01
535
(0.0 - E3-04)
Determined by E3-01
535
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
0.0 Hz
536
(0.0 - E3-04)
0.0 V
536
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
0.0 V
536
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
Default
Ref.
(Range)
Determined by o2-04,
536
C6-01
(10% to 200% of the
drive rated current)
Determined by o2-04,
537
C6-01
(0.000 - 20.000 Hz)
Determined by o2-04,
537
C6-01
(0 to E4-01)
4
537
(2 - 120)
Determined by o2-04,
537
C6-01
(0.000 - 65.000 Ω)
Determined by o2-04,
538
C6-01
(0.0 - 60.0%)
0.50
538
(0.00 - 0.50)
0.75
538
(E4-07 - 0.75)
0.0%
538
(0.0 - 10.0%)
Determined by o2-04,
538
C6-01
(0 - 65535 W)
Determined by o2-04,
538
C6-01
(0.00 - 650.00 kW)
337
11

Advertisement