6 Vector Control and Applied Functions
6-1-2

Offline Auto-tuning for Motor Parameters

• Use this function to measure and automatically set the motor parameters required for sensorless
vector control.
• To use the sensorless vector control method, perform auto-tuning to measure the motor parameter
values.
• The measured motor parameter values will be set as 50-Hz converted data for one phase in Y-con-
nection.
Parameter
No.
H001
Auto-tuning Selection
1st/2nd Motor Parame-
H002/H202
ter Selection
H003/H203
1st/2nd Motor Capacity
1st/2nd Motor Pole
H004/H204
Number
1st/2nd Motor Parame-
H030/H230
ter R1 (Auto-tuning
Data)
1st/2nd Motor Parame-
H031/H231
ter R2 (Auto-tuning
Data)
1st/2nd Motor Parame-
H032/H232
ter L (Auto-tuning Data)
1st/2nd Motor Parame-
H033/H233
ter lo (Auto-tuning
Data)
1st/2nd Motor Parame-
H034/H234
ter J (Auto-tuning Data)
A003/A203
1st/2nd Base Frequency
DC Injection Braking
A051
Selection
1st/2nd Motor Rated
A082/A282
Voltage Selection
b033
Motor Cable Length
6 - 4
Function name
00:
Disabled
01:
Enabled (No motor rotation)
02:
Enabled (Motor rotation)
00:
Standard motor parameter
02:
Auto-tuning parameter (Applies
H030/H230 to H034/H234 data to motor
parameters.)
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/5.5/
7.5/11.0/15.0/18.5
2/4/6/8
10 to 488: Do not set.
0.001 to 65.535
0.01 to 655.35
0.01 to 655.35
0.001 to 9999.000
30.0 to 1st/2nd Maximum Frequency
(A004/A204)
00:
Disabled
01:
Enabled
02:
Enabled (Operates only at set frequency)
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
5. to 20.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Data
Default
Unit
data
00
00
Maximum
applicable
kW
motor
capacity
4
pole
Depen-
dent on
motor
mH
capacity
A
2
kgm
60.0
Hz
00
200/400
V
10.
m