Omron Q2V Series Technical Manual page 617

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

12: AcDcTimeGain
Setting Value
Function
12
AcDcTimeGain
When you enable C1-01 [Accel Time 1], the acceleration time is:
Acceleration Time 1 = Setting value of C1-01 × acceleration and deceleration time gain / 100
Figure 12.94 Acceleration/Deceleration Time Gain through Analog Input
13: DCInjBrakCurr
Setting Value
Function
13
DCInjBrakCurr
Note:
When you set this function, it will disable the setting value of b2-02 [DCI Braking Current].
14: StallPLev@Rn
Setting Value
Function
14
StallPLev@Rn
Note:
The drive will use the smaller value of these values for Stall Prevent Level during Run:
• Multi-function analog input terminal analog input value
• L3-06 [StallP Level@Run]
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the gain used for C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4] and C1-09 [Fast Stop Time]
when the full scale analog signal (10 V or 20 mA) is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Figure 12.95 DC Injection Braking Current through Analog Input
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Figure 12.96 Stall Prevention Level during Run with Analog Input
12.7 H: TERMINALS
Description
Description
Description
12
617