Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

41: KEB Thru1 NO
Setting Value
Function
41
KEB Thru1 NO
ON : Deceleration during momentary power loss
OFF : Normal operation
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method]. The drive operates with the selected KEB method.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to
"KEB Ride-Thru Function on page
42: KEB Thru2 NC
Setting Value
Function
42
KEB Thru2 NC
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method] setting will not have an effect.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to
"KEB Ride-Thru Function on page
43: KEB Thru2 NO
Setting Value
Function
43
KEB Thru2 NO
ON : Deceleration during momentary power loss
OFF : Normal operation
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method] setting will not have an effect.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to
"KEB Ride-Thru Function on page
44: Field weakening
Setting Value
Function
44
Field weakening
Note:
"d6: FIELD WEAKENING / FORCING on page
Refer to
45: ASR Gain Switch
Setting Value
Function
45
ASR Gain Switch
ON : C5-03
Switches the proportional gain to C5-03 [ASR PGain 2].
OFF : C5-01
Switches the proportional gain to C5-01 [ASR PGain 1].
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
637" for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
637" for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
637" for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01[Field Weak
Level] and d6-02 [Field Weak FqLimit] when the input terminal is activated.
522" for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to switch the ASR proportional gain set in C5-01 [ASR PGain 1] and C5-03 [ASR PGain 2].