Omron Q2V Series Technical Manual page 659

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

• When you manually clear a fault after the drive triggers protective functions.
• When you re-energize the drive.
L5-02: Fault@Reset Select
No.
Name
(Hex.)
L5-02
Fault@Reset Select
(049F)
1 : Disable Fault Output
2 : Enable Fault Output
L5-04: Interval Reset Time
No.
Name
(Hex.)
L5-04
Interval Reset Time
(046C)
L5-05: Reset Method
No.
Name
(Hex.)
L5-05
Reset Method
(0467)
1 : Continuous
Counts the number of successful fault resets through Auto Restart.
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
2 : Use L5-04 Time
Counts the number of all fault resets (successful and unsuccessful) through Auto Restart. The drive repeats the
Auto Restart process in the intervals set in L5-04 [Interval Reset Time].
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
L5-07: OL1-4 Auto-Reset Select
No.
Name
(Hex.)
L5-07
OL1-4 Auto-Reset Select
(0B2A)
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = 3] while the
drive is automatically restarting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time interval between each Auto Restart attempt. This function is enabled when L5-05 =
2 [Reset Method = Use L5-04 Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the count method for the Auto Restart operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set
oL1, oL2, oL3, and oL4, in order.
Description
Description
Description
Description
12.8 L: PROTECTION
Default
(Range)
1
(1, 2)
Default
(Range)
10.0 s
(0.5 - 600.0 s)
Default
(Range)
1
(1, 2)
Default
(Range)
1111