Omron Q2V Series Technical Manual page 299

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Item
V/f Characteristics
Select from 15 pre-defined V/f patterns, or a user-set V/f pattern.
Feed Forward Control, Restart After Momentary Power Loss, Speed Search, Overtorque Detection, Torque Limit, 17 Step Speed (max.), Accel/Decel
Switch, S-curve Acceleration/Deceleration, 3-wire Sequence, Auto-Tuning (Rotational and Stationary), Dwell Function, Cooling Fan ON/OFF Switch,
Main Control
Slip Compensation, Torque Compensation, Frequency Jump, Upper/Lower Limits for Frequency Reference, DC Injection Braking at Start and Stop,
Functions
Overexcitation Braking, High Slip Braking, PID Control (with Sleep Function), Energy Saving Control, Modbus Communications (RS-485 max, 115.2
kbps), Auto Restart, Application Presets, Q2pack (customized functions), Parameter Backup Function, Online Tuning, KEB, Overexcitation
Deceleration, Overvoltage Suppression, High Frequency Injection, etc.
Item
Electronic thermal overload protection
Motor Protection
Drive stops when the output current is more than 200% of the HD output current.
Momentary
Overcurrent
Note:
Protection
Standard value is 200%. Different capacity drives have different values.
Drive stops when the output current is more than these overload tolerances:
• HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
Overload Protection
• ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
Note:
If output frequency < 6 Hz, the drive can trigger the overload protection function when the output current is in the overload tolerance range.
Overvoltage
200 V class: Stops when the DC bus voltage is more than approximately 410 V
Protection
400 V class: Stops when the DC bus voltage is more than approximately 820 V
Three-phase 200 V class: Stops when the DC bus voltage decreases to less than approximately 190 V
Undervoltage
Single-phase 200 V class: Stops when the DC bus voltage decreases to less than approximately 160 V
Protection
Three-phase 400 V class: Stops when the DC bus voltage decreases to less than approximately 380 V
Stops when power loss is longer than 15 ms and continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
Momentary Power
• Stop time may be shortened depending on the load and motor speed.
Loss Ride-thru
• Drive capacity will change the continuous operation time. A Momentary Power Loss Recovery Unit is necessary to continue operation through a 2 s
power loss on models 2001 to 2042 and 4001 to 4023.
Heatsink Overheat
Thermistor
Protection
Braking Resistor
Overheat detection for braking resistor (optional ERF-type, 3% ED)
Overheat Protection
Stall prevention is available during acceleration, deceleration, and during run.
Stall Prevention
Electronic circuit protection
Note:
Ground Fault
This protection detects ground faults during run. The drive will not provide protection when:
Protection
• There is a low-resistance ground fault for the motor cable or terminal block
• Energizing the drive when there is a ground fault.
DC Bus Charge LED Charge LED illuminates when DC bus voltage is more than 50 V.
Item
Area of Use
Indoors
Overcurrent Category III
Power Supply
IP20/UL Open Type: -10°C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
Ambient
Temperature Setting
• When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
95% RH or less
Humidity
Do not let condensation form on the drive.
Storage Temperature -20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
Surrounding Area
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
SIEPCYEUOQ2V01A Q2V Technical Manual
Specification
Table 10.9 Protection Functions
Specification
Table 10.10 Environment
Specification
10.6 Drive Specifications
299
10