Omron Q2V Series Technical Manual page 643

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

L2-04: Powloss Ramp Time@recovery
No.
Name
(Hex.)
L2-04
Powloss Ramp
Time@recovery
(0488)
Sets the time for voltage to recover from 0 V to the value set in E1-05 [Max Output Voltage].
L2-05: UV Detection Lvl (Uv1)
No.
Name
(Hex.)
L2-05
UV Detection Lvl (Uv1)
(0489)
NOTICE: Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
Note:
If the low voltage detection level is near the lower limit value of L2-05, the drive will detect Uv1 during KEB Ride-Thru operation. Do
not set the value too low when you use the KEB Ride-Thru function.
L2-06: KEB Decel Time
No.
Name
(Hex.)
L2-06
KEB Decel Time
(048A)
Expert
Set L2-29 = 3 or 4 [KEB Method = System KEB1 Ride-Thru or System KEB2 Ride-Thru] to enable this function.
When L2-29 = 2 , 3, 4 [Single KEB2 Ride-Thru, System KEB1 Ride-Thru, System KEB2 Ride-Thru] and you do
KEB Auto-Tuning, the drive will automatically set this value.
Sets the deceleration time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. If a Uv1 [DC Bus Undervoltage] fault occurs during KEB operation, decrease the
deceleration time. If an ov [Overvoltage] fault occurs, increase the deceleration time.
• L2-06 = 0
The drive automatically decreases C1-09 [Fast Stop Time] to the base value to keep the DC bus voltage above
the low voltage detection level. The drive ignores L2-02 [RideThrough Time@Power Loss] in this condition.
• L2-06 ≠ 0
As shown in
Figure
12.115, the frequency reference decelerates to the KEB frequency level as specified by the
deceleration rate set in L2-06 and then returns to the initial frequency reference as specified by C1-01 [Accel
Time 1]. The drive uses the setting value of the KEB frequency rate as shown in the this formula to set the KEB
frequency level:
KEB frequency level = Output frequency before power loss × (1 - (L2-02)/(L2-06))
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time for the drive output voltage to go back to correct voltage after completing speed
searches.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the voltage at which a Uv1 [DC Bus Undervoltage] fault is triggered or at which the KEB
function is activated. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the deceleration time during KEB operation used to decrease the maximum output frequency
to 0.
Figure 12.115 Kinetic Energy Backup Decel Time
Description
Description
Description
12.8 L: PROTECTION
Default
(Range)
Determined by o2-04, C6-
01
(0.0 - 5.0 s)
Default
(Range)
Determined by o2-04 and
E1-01
(200 V Class: 150 - 210 V,
400 V Class: 300 - 420 V)
Default
(Range)
0.0 s
(0.0 - 6000.0 s)
643