4 : ILim Mode
This function uses the L3-02 value to limit the output current and automatically adjusts the acceleration rate.
When the load (output current) increases to more than the current limit level during acceleration, the drive
automatically adjusts the acceleration rate.
L3-02: StallP Level@Accel
No.
Name
(Hex.)
L3-02
StallP Level@Accel
(0490)
Note:
• If you use a motor that is small compared to the drive and the motor stalls, decrease the setting value.
• When you operate the motor in the constant power range, set L3-03 [StallP Limit@Accel].
• The upper limit to the setting range changes when the setting for C6-01 [ND/HD Duty Selection] changes.
– 150% when C6-01 = 0 [HD Rating]
– 120% when C6-01 = 1 [ND Rating]
L3-03: StallP Limit@Accel
No.
Name
(Hex.)
L3-03
StallP Limit@Accel
(0491)
The stall prevention level set in L3-02 [StallP Level@Accel] is automatically reduced when the motor is running
within the constant output range. Parameter L3-03 is the limit value used to prevent the stall prevention level
during constant output ranges to fall below the minimum required level.
Note:
The function to automatically reduce the stall prevention level does not operate when L3-01 = 4 [StallP Mode@Accel = ILim Mode].
L3-04: StallP@Decel Enable
No.
Name
(Hex.)
L3-04
StallP@Decel Enable
(0492)
SIEPCYEUOQ2V01A Q2V Technical Manual
Figure 12.118 Current Limit Acceleration
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the output current level at which the Stall Prevention function operates during acceleration
where the drive rated output current is 100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit for the stall prevention level used in the constant output range as a percentage
of the drive rated output current.
Figure 12.119 Stall Prevent Level during Accel/Limit
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enables Stall Prevention during deceleration.
Description
Description
Description
12.8 L: PROTECTION
Default
(Range)
Determined by C6-01 and
L8-38
(0 - 150%)
Default
(Range)
50%
(0 - 100%)
Default
(Range)
1
(0, 1)
649