12.7 H: TERMINALS
H2-07: Mbus Reg1 Address Select
No.
Name
(Hex.)
H2-07
Mbus Reg1 Address Select
(0B3A)
Sets the address of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the bit in H2-08
[Mbus Reg1 Bit Select].
H2-08: Mbus Reg1 Bit Select
No.
Name
(Hex.)
H2-08
Mbus Reg1 Bit Select
(0B3B)
Sets the bit of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the address in H2-07
[Mbus Reg1 Address Select].
H2-09: Mbus Reg2 Address Select
No.
Name
(Hex.)
H2-09
Mbus Reg2 Address Select
(0B3C)
Sets the address of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the bit in H2-10
[Mbus Reg2 Bit Select].
H2-10: Mbus Reg2 Bit Select
No.
Name
(Hex.)
H2-10
Mbus Reg2 Bit Select
(0B3D)
Sets the bit of the register that is output to ModbusReg 1 [H2-01 to H2-03 = 67] and uses the address in H2-09
[Mbus Reg2 Address Select].
H2-20: Compare1 Mon.Selection
No.
Name
(Hex.)
H2-20
Compare1 Mon.Selection
(1540)
Note:
• For information on the comparator function, refer to
• The configurable monitor changes when the control method changes.
H2-21: Compare1 Low Limit
No.
Name
(Hex.)
H2-21
Compare1 Low Limit
(1541)
Note:
For information on the comparator function, refer to
H2-22: Compare1 Up Limit
No.
Name
(Hex.)
H2-22
Compare1 Up Limit
(1542)
590
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example,
set H2-20 = 102 to monitor U1-02 [Output Frequency].
3C: Comparator 1 on page 605
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
3C: Comparator 1 on page 605
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
Description
Description
Description
Description
Description
and
3D: Comparator 2 on page
Description
and
3D: Comparator 2 on page
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
102
(000 - 999)
605.
Default
(Range)
0.0%
(0.0 - 300.0%)
605.
Default
(Range)
0.0%
(0.0 - 300.0%)

Advertisement

Table of Contents
loading

Table of Contents