Omron Q2V Series Technical Manual page 641

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Parameters for KEB Ride-Thru
This table shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in L2-29 [KEB Method].
No.
Name
C1-09
Fast Stop Time
C2-03
Jerk@Start of Decel
L2-05
UV Detection Lvl (Uv1)
L2-06
KEB Decel Time
L2-07
KEB Accel Time
L2-08
Frq.Gain@KEB Start
L2-10
Minimum KEB Time
L2-11
KEB DC Volt Setpoint
L3-20
DCBus VoltAdj Gain
L3-21
OVSup Acc/Dec Gain
SIEPCYEUOQ2V01A Q2V Technical Manual
Figure 12.114 KEB Function Wiring Example
Table 12.50 Parameters for KEB Ride-Thru
Configuring Settings
• If ov [Overvoltage] occurs during KEB deceleration, increase the setting value.
• If Uv1 [DC Bus Undervoltage] occurs during KEB deceleration, decrease the
setting value.
• If ov occurs immediately after you start KEB deceleration, increase the setting
value.
• If Uv1 occurs immediately after you start KEB deceleration, decrease the
setting value.
If Uv1 occurs immediately after you start KEB deceleration, increase the setting
value to detect power loss more quickly.
• Kinetic Energy Backup Decel Time
• If ov or Uv1 occur during KEB deceleration after KEB Tuning, set L2-06 in
these conditions:
– If ov occurs, increase the setting value
– If Uv1 occurs, decrease the setting value.
Sets the acceleration time to return to the frequency reference value before a
power loss, after you cancel the KEB operation. When L2-07 = 0, the drive uses
the standard acceleration times set in C1-01, C1-03, C1-05, and C1-07
[Acceleration Time].
• If ov occurs immediately after you start operation, decrease the setting value.
• If Uv1 occurs immediately after you start operation, increase the setting value.
• With KEB Ride-Thru
There is Uv1 because you set a digital input for KEB Ride-Thru and the device
that controls the input operated too slowly after power loss.
• Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts,
increase L2-10 to longer than the overshoot.
• Single Drive KEB Ride-Thru 2
Set to approximately 1.22 x input voltage.
• Single Drive KEB Ride-Thru 1, System KEB Ride-Thru 1, or System KEB
Ride-Thru 2
Set to approximately 1.4 x input voltage.
• If ov or Uv1 occurs at the start of deceleration when you use KEB operation,
increase this value in 0.1-unit increments.
• If there is torque ripple during deceleration when you use KEB Ride-Thru,
decrease the value.
If there is large speed or current ripple, decrease the value in 0.05 unit increments.
Note:
If the setting value is too low, then the drive will have unsatisfactory DC bus
voltage control response. The drive can detect ov or Uv1.
12.8 L: PROTECTION
L2-29 [Kinetic Energy Backup Method]
0
1
2
*1
x
-
-
x
-
x
x
x
x
*2
-
-
x
x
x
x
x
x
-
x
x
x
x
x
x
x
-
x
-
-
x
-
3
-
x
x
*2
x
x
x
x
-
12
-
641