Parameters
List of Parameters
p0844[0...2]
BI: 1. OFF2 / 1. OFF2
CU240S PN
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines first source of OFF2 when P0719 = 0 (BICO).
Dependency:
If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
OFF2 means immediate pulse-disabling; the motor is coasting.
Note:
OFF2 is low-active, i.e. :
0 = Pulse disabling.
1 = Operating condition.
p0845[0...2]
BI: 2. OFF2 / 2. OFF2
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Defines second source of OFF2.
Description:
Dependency:
In contrast to P0844 (first source of OFF2), this parameter is always active, independent of P0719 (selection of
command and frequency setpoint).
If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.
Note:
OFF2 means immediate pulse-disabling; the motor is coasting.
OFF2 is low-active, i.e. :
0 = Pulse disabling.
1 = Operating condition.
p0848[0...2]
BI: 1. OFF3 / 1. OFF3
CU240E
Access level: 3
CU240S
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines first source of OFF3 when P0719 = 0 (BICO).
Dependency:
If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Note:
OFF3 means quick ramp-down to 0.
OFF3 is low-active, i.e.
0 = Quick ramp-down.
1 = Operating condition.
1-98
P-Group: Commands
Active: NO
Max
-
P-Group: Commands
Active: NO
Max
-
P-Group: Commands
Active: NO
Max
-
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned32
Data set: CDS
Factory setting
8890.1
Data type: Unsigned32
Data set: CDS
Factory setting
19.1
Data type: Unsigned32
Data set: CDS
Factory setting
1