Siemens Sinamics G120 Series Parameter Manual page 156

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
f
max
1
4
no synchronuos motor
Recommended means of commissioning:
For correct operation under SLVC / VC control it is imperative that the name plate data of the motor (P0304 -
P0310) is correctly entered and that the motor data identification (P1900) must be carried out on a cold motor.
It is also necessary to ensure that the motor ambient temperature is correctly entered in P0625 if this is significantly
different from the default value of 20°C.
This must be done after the quick commissioning has been completed (P3900) but before the motor data identifica-
tion measurements are carried out.
Optimisation:
The following parameters can be adjusted by the user to improve performance.
P0003 = 3
P0342: Total / motor inertia ratio
Sensorless Vector Control (SLVC):
P1470: P gain (SLVC)
P1472: I term (SLVC)
P1610: Continuous torque boost (SLVC, open loop boost)
P1750: Control word of motor model
Vector Control (VC):
P1460: P gain
P1462: I term
The following table presents an overview of control parameters (SLVC, VC) that can be modified in relationship to
P1300 dependencies:
1-156
= min(200 Hz, 5 p0310)
(max. frequency)
p0305
r0209
(ratio of rated motor current to rated inverter current)
r0207
r0207
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240s dpCu240s dp-fCu240sCu240s pn

Table of Contents