Siemens Sinamics G120 Series Parameter Manual page 22

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
r0032
CO: Act. filtered power / Act fil. power
Access level: 2
Unit: -
Description:
Displays motor power.
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0035[0...2]
CO: Act. motor temperature / Act. mot.temp.
Access level: 2
Unit: [°C]
Description:
Displays measured motor temperature.
r0036
CO: Inverter overload utilization / Invert ovl util
Access level: 4
Unit: [%]
Description:
Displays inverter overload utilization calculated via the I2t model.
The actual I2t value relative to the max. possible I2t value supplies utilization in [%].
If the current exceeds the threshold for P0294 (inverter I2t overload warning), alarm A0505 (inverter I2t) is gener-
ated and the output current of the inverter reduced via P0290 (inverter overload reaction).
If 100 % utilization is exceeded, alarm F0005 (inverter I2t) is tripped.
Example:
Normalized output current
p0294 (95 %)
Dependency:
r0036 > 0:
If the nominal current (see r0207) of the inverter is exceed, utilization will be displayed, otherwise, 0 % utilization is
displayed.
1-22
ω, M
Motor
r0027
r0207
100 %
i
2
t [%]
r0036
A0505
1
0
P-Group: Closed-loop control
=
ω
=
⋅ π
P
M
2
f
M
mech
1
r0022
=
r0032
[kW]
2
π
1000
r0032
[hp]
=
0.75
r0032
[kW]
P-Group: Motor
P-Group: Converter
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Floating Point
Data set: -
[1/min]
r0031
[Nm]
60
Data type: Floating Point
Data set: DDS
Data type: Floating Point
Data set: -
Reaction via p0290
Default: "current reduction"
t
t
t
© Siemens AG 2007 All Rights Reserved