Siemens Sinamics G120 Series Parameter Manual page 114

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

Parameters
List of Parameters
p1000[0...2]
Selection of frequency setpoint / Freq setp. select.
CU240S DP
Access level: 1
CU240S DP-F
Quick comm. YES
CU240S PN
Can be changed: C, T
Min
0
Description:
Selects frequency setpoint source.
The selection of settings is detailed in the following table of values, in which the main setpoint is given by the least
significant digit (right-hand position) and the additional setpoint is given by the most significant digit (left-hand posi-
tion). Single digits denote main setpoints that have no additional setpoint.
Values:
0:
1:
2:
3:
4:
6:
7:
10:
11:
12:
13:
14:
16:
17:
20:
21:
22:
23:
24:
26:
27:
30:
31:
32:
33:
34:
36:
37:
40:
41:
42:
43:
44:
46:
47:
60:
61:
62:
63:
64:
66:
67:
70:
71:
72:
73:
74:
76:
77:
Caution:
Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P1070, P1071, P1075, P1076
1-114
No main setpoint
MOP setpoint
Analog setpoint
Fixed frequency
USS on RS232
Fieldbus
Analog setpoint 2
No main setpoint + MOP setpoint
MOP setpoint
+ MOP setpoint
Analog setpoint
+ MOP setpoint
Fixed frequency
+ MOP setpoint
USS on RS232
+ MOP setpoint
Fieldbus
+ MOP setpoint
Analog setpoint 2 + MOP setpoint
No main setpoint + Analog setpoint
MOP setpoint
+ Analog setpoint
Analog setpoint
+ Analog setpoint
Fixed frequency
+ Analog setpoint
USS on RS232
+ Analog setpoint
Fieldbus
+ Analog setpoint
Analog setpoint 2 + Analog setpoint
No main setpoint + Fixed frequency
MOP setpoint
+ Fixed frequency
Analog setpoint
+ Fixed frequency
Fixed frequency
+ Fixed frequency
USS on RS232
+ Fixed frequency
Fieldbus
+ Fixed frequency
Analog setpoint 2 + Fixed frequency
No main setpoint + USS on RS232
MOP setpoint
+ USS on RS232
Analog setpoint
+ USS on RS232
Fixed frequency
+ USS on RS232
USS on RS232
+ USS on RS232
Fieldbus
+ USS on RS232
Analog setpoint 2 + USS on RS232
No main setpoint
+ Fieldbus
MOP setpoint
+ Fieldbus
Analog setpoint
+ Fieldbus
Fixed frequency
+ Fieldbus
USS on RS232
+ Fieldbus
Fieldbus
+ Fieldbus
Analog setpoint 2 + Fieldbus
No main setpoint
+ Analog setpoint 2
MOP setpoint
+ Analog setpoint 2
Analog setpoint
+ Analog setpoint 2
Fixed frequency
+ Analog setpoint 2
USS on RS232
+ Analog setpoint 2
Fieldbus
+ Analog setpoint 2
Analog setpoint 2
+ Analog setpoint 2
P-Group: Setpoints
Active: NO
Max
77
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned16
Data set: CDS
Factory setting
6