p2242[0...2]
CI: PID-MOP auto setpoint / PMOP auto setpoint
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P2241 is selected.
Notice:
Refer to: P2241
p2243[0...2]
BI: PID-MOP accept rampgenerator setpoint / PMOP acc RFG setpo
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Sets the signal source for the setting command to accept the setting value for the motorized potentiometer. The
value becomes effective for a 0/1 edge of the setting command.
Notice:
Refer to: P2244
p2244[0...2]
CI: PID-MOP rampgenerator setpoint / PMOP RFG setpoint
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of the setting
command.
Notice:
Refer to: P2243
r2245
CO: PID-MOP input frequency of the RFG / PMOP RFG input
Access level: 3
Unit: [%]
Description:
Displays the motorized potentiometer setpoint before it passed the PID-MOP RFG.
p2247[0...2]
PID-MOP ramp-up time of the RFG / PMOP ramp-up time
Access level: 2
Quick comm. NO
Can be changed: U, T
Min
0.00 [s]
Description:
Sets the ramp-up time for the internal PID-MOP ramp-function generator.
The setpoint is changed from zero up to limit defined in P1082 within this time.
Notice:
Refer to: P2248, P1082
1-244
P-Group: Technology
Active: NO
Max
-
P-Group: Technology
Active: NO
Max
-
P-Group: Technology
Active: NO
Max
-
P-Group: Technology
P-Group: Technology
Active: NO
Max
1000.00 [s]
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned32
Data set: CDS
Factory setting
0
Data type: Unsigned32
Data set: CDS
Factory setting
0
Data type: Unsigned32
Data set: CDS
Factory setting
0
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: DDS
Factory setting
10.00 [s]