p1082[0...2]
Max. frequency / Max. frequency
CU240E
Access level: 1
CU240S
Quick comm. YES
Can be changed: C, T
Min
0.00 [Hz]
Description:
Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint.
The value set here is valid for both clockwise and anticlockwise rotation. Futhermore, the monitoring function |f_act|
>= P1082 (r0052 Bit10, see example below) is affected by this parameter.
Example:
p1082 - p2162
|f_act| ≥ p1082 (f_max)
Dependency:
The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min(15*P0310, 650 Hz).
As consequence P1082 can be affected if P0310 is changed to a smaller value.
The maximum frequency and the pulse frequency depending on each other. The maximum frequency affects the
pulse frequency according to the following table.
f
max
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6 kHz the
parameter is changed P1800 = 6 kHz.
The maximum output frequency of inverter can be exceeded if one of the following is active:
- p1335 ≠ 0
f
- p1200 ≠ 0
f
The resultant value is displayed in r1084 (resultant maximum frequency).
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
⏐f_act⏐
p1082
1
r0052
Bit 10
0
2 kHz
0 - 133.3 Hz
0 - 266.6 Hz
p1082
(Slip compensation active) :
=
+
(p1335)
f
f
max
max
slip
,
max
(Flying restart active) :
=
+
(p1200)
f
2
f
max
max
slip
,
nom
P-Group: Setpoints
Active: NO
Max
650.00 [Hz]
p1800
4 kHz
6 kHz
0 - 400 Hz
p1336
r0330
=
+
p1082
p0310
100
100
r0330
=
+
p1082
2
p0310
100
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Factory setting
50.00 [Hz]
8 - 16 kHz
0 - 650 Hz
t
t
1-129