r1917[0...2]
Identified stator inductance 2 / Stator induct. 2
Access level: 2
Unit: -
Description:
Displays identified stator inductance. [mH]
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
Note:
See P1915 (identified nominal stator inductance)
r1918[0...2]
Identified stator inductance 3 / Stator induct. 3
Access level: 2
Unit: -
Description:
Displays identified stator inductance. [mH]
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
Note:
See P1915 (identified nominal stator reactance)
r1919[0...2]
Identified stator inductance 4 / Stator induct. 4
Access level: 2
Unit: -
Description:
Displays identified stator inductance. [mH]
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
Note:
See P1915 (identified nominal stator inductance)
r1920[0...2]
Identified dyn. leak. inductance / Dyn. leak. induct.
Access level: 2
Unit: -
Description:
Displays identified total dynamic leakage inductance.
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
r1925[0...2]
Identified on-state voltage / Id. on-state V.
Access level: 2
Unit: [V]
Description:
Displays identified on-state voltage of IGBT. [V]
Index:
[0] = U_phase
[1] = V_phase
[2] = W_phase
Notice:
If the identified on-state voltage does not lie within the range 0.0V < 10V fault message 41 (motor data identification
failure) is issued.
P0949 provides further information (fault value = 20 in this case).
r1926
Ident. gating unit dead time / Id.gating deadtime
Access level: 2
Unit: [µs]
Description:
Displays identified dead time of gating unit interlock. [usec]
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Motor identification
P-Group: Motor identification
P-Group: Motor identification
P-Group: Motor identification
P-Group: Motor identification
P-Group: Motor identification
Parameters
List of Parameters
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
Data type: Floating Point
Data set: -
1-193

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240s dpCu240s dp-fCu240sCu240s pn

Table of Contents