p1135[0...2]
OFF3 ramp-down time / OFF3 ramp-dwn time
Access level: 2
Quick comm. YES
Can be changed: C, U, T
Min
0.00 [s]
Description:
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
Note:
This time may be exceeded if the VDC_max. level is reached.
p1140[0...2]
BI: RFG enable / RFG enable
CU240E
Access level: 3
CU240S
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
Dependency:
When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
p1140[0...2]
BI: RFG enable / RFG enable
CU240S DP
Access level: 3
CU240S DP-F
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
Dependency:
p1140[0...2]
BI: RFG enable / RFG enable
CU240S PN
Access level: 3
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
Dependency:
When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
p1141[0...2]
BI: RFG start / RFG start
CU240E
Access level: 3
CU240S
Quick comm. NO
Can be changed: T
Min
-
Description:
Defines command source of RFG start command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output is held at its present value.
Dependency:
When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Setpoints
Active: NO
Max
650.00 [s]
P-Group: Commands
Active: NO
Max
-
P-Group: Commands
Active: NO
Max
-
P-Group: Commands
Active: NO
Max
-
P-Group: Commands
Active: NO
Max
-
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Factory setting
5.00 [s]
Data type: Unsigned32
Data set: CDS
Factory setting
1
Data type: Unsigned32
Data set: CDS
Factory setting
2090.4
Data type: Unsigned32
Data set: CDS
Factory setting
8890.4
Data type: Unsigned32
Data set: CDS
Factory setting
1
1-137