Faults and Alarms
List of Fault and Alarm messages
F00055
BOP-EEPROM Fault
Reaction:
OFF 2 (OFF 3)
Acknowledge:
Quit fault eg. via DI2
Cause:
Read or write failure while saving non-volatile parameter to EEPROM on BOP whilst parameter cloning.
Remedy:
•
Factory Reset and new parameterization
•
Change BOP
•
r0949 = 5096 : Use a BOP with a bigger EEPROM
•
r0949 = 9160 : Use a BOP with a smaller EEPROM
Note:
•
r0949 = 1000 + Block No: Reading data block failed
•
r0949 = 3000 + Block No: Reading data block CRC failed
•
r0949 = 4000 + Block No: Writing data block failed
•
r0949 = 5096 : BOP EEPROM too Small
•
r0949 = 6000 + Block No: writing data block verify failed
•
r0949 = 7000 + Block No: Reading data block at wrong time
•
r0949 = 8000 + Block No: writing data block at wrong time
•
r0949 = 9160 : Drive EEPROM too Small
F00056
BOP not fitted
Reaction:
OFF 2 (OFF 3)
Acknowledge:
Quit fault eg. via DI2
Cause:
Trying to initiate parameter cloning without BOP fitted.
Remedy:
Fit BOP and try again.
F00057
BOP fault
Reaction:
OFF 2 (OFF 3)
Acknowledge:
Quit fault eg. via DI2
Cause:
•
Parameter cloning with empty BOP.
•
Parameter cloning with invalid BOP.
Remedy:
Download to BOP or replace BOP.
F00058
BOP contents incompatible
Reaction:
OFF 2 (OFF 3)
Acknowledge:
Quit fault eg. via DI2
Cause:
Trying to initiate parameter cloning with BOP created on another type of drive.
Remedy:
Download to BOP from this type of drive.
F00060
Asic Timeout
Reaction:
OFF 2
Acknowledge:
Quit fault eg. via DI2
Cause:
Internal communications failure
•
r0949 = 0: HW reported Link Fail
•
r0949 = 1: SW reported Link Fail
Remedy:
Check connection between inverter power module and inverter control unit
Fault appears sporadically:
•
Communication failure due to EMC problems
•
Check - and if necessary - improve EMC
•
Use EMC filter
Fault appears immediately when mains voltage is applied and an ON command is given.
•
If fault persists, change inverter.
•
Contact Service Department.
3-386
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007