r2053[0...7]
FB identification / FB identification
CU240S DP
Access level: 3
CU240S DP-F
Unit: -
Description:
Displays identification data of the communication.
2053[0]: = 0 = No communication option available
2053[0]: = 1 = PROFIBUS DP
2053[0]: = 2 = DeviceNet
2053[0]: = 3 = CAN
2053[0]: = 4 = AS-i
2053[0]: = 5 = LON
2053[0]: = 6 = Modbus
2053[0]: = 10 = PROFINET IO
2053[0]: = 11 = ES bus (ET200pro)
2053[0]: = 4660 = ES bus (ET200s)
2053[0]: = 65535 = not defined
2053[1]: firmware version (major and minor each with 2 digits)
2053[2]: firmware version detail (release and build each with 2 digits)
2053[3]: firmware date (year with century)
2053[4]: firmware date (day and month each with 2 digits)
2053[5]: datastructure version
2053[6]: driver version
2053[7]: company ID (42 = SIEMENS)
Index:
[0] = Fieldbus type (PROFIBUS = 1)
[1] = Firmware version
[2] = Firmware version detail
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = datastructure version
[6] = driver version
[7] = company ID
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Communications
Parameters
List of Parameters
Data type: Unsigned16
Data set: -