p0367[0...2]
Magnetizing curve imag 2 / Magnet.curve imag2
Access level: 4
Quick comm. NO
Can be changed: U, T
Min
20.0 [%]
Description:
Specifies second magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the second value pair of the characteristic.
Dependency:
Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
p0368[0...2]
Magnetizing curve imag 3 / Magnet.curve imag3
Access level: 4
Quick comm. NO
Can be changed: U, T
Min
20.0 [%]
Description:
Specifies third magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the third value pair of the characteristic.
Dependency:
Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
p0369[0...2]
Magnetizing curve imag 4 / Magnet.curve imag4
Access level: 4
Quick comm. NO
Can be changed: U, T
Min
20.0 [%]
Description:
Specifies fourth magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the fourth value pair of the characteristic.
Dependency:
Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
r0370[0...2]
Stator resistance [%] / Stator res. [%]
Access level: 4
Unit: [%]
Description:
Displays standardized stator resistance of motor equivalent circuit (phase value) in [%].
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Motor
Active: YES
Max
250.0 [%]
P-Group: Motor
Active: YES
Max
250.0 [%]
P-Group: Motor
Active: YES
Max
250.0 [%]
P-Group: Motor
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Factory setting
75.0 [%]
Data type: Floating Point
Data set: DDS
Factory setting
135.0 [%]
Data type: Floating Point
Data set: DDS
Factory setting
170.0 [%]
Data type: Floating Point
Data set: DDS
1-53