Parameters
List of Parameters
p0700[0...2]
Selection of command source / Command source sel
CU240S DP
Access level: 1
CU240S DP-F
Quick comm. YES
CU240S PN
Can be changed: C, T
Min
0
Description:
Selects digital command source.
Values:
0:
1:
2:
4:
6:
Dependency:
Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P0701, ... (function of DI), P0731, P0732, P0733, P0800, P0801, P0840, P0842, P0844, P0845, P0848, P0849,
P0852, P1020, P1021, P1022, P1023, P1035, P1036, P1055, P1056, P1074, P1110, P1113, P1124, P1140,
P1141, P1142, P1230, P1477, P1501, P2103, P2104, P2106, P2200, P2220, P2221, P2222, P2223, P2226,
P2228, P2235, P2236
Caution:
Be aware, by changing of parameter P0700 all BI parameters are reset to the default value.
p0701[0...2]
Function of digital input 0 / Function of DI0
CU240E
Access level: 2
CU240S
Quick comm. NO
PM240
Can be changed: T
Min
0
Description:
Selects function of digital input 0.
Values:
0:
1:
2:
3:
4:
9:
10:
11:
12:
13:
14:
15:
16:
17:
18:
25:
27:
29:
33:
99:
Dependency:
Setting 99 (enable BICO parameterization) requires:
P0700 command source or
P0010 = 1, P3900 = 1, 2 or 3 (quick commissioning) or
P0010 = 30, P0970 = 1 factory reset in order to reset
Note:
"ON/OFF1" can only be selected for one digital input (e.g. P0700 = 2 and P0701 = 1).
Configuring DI1 with P0702 = 1 will disable DI0 by setting P0701 = 0. Only the last activated digital input serves as
a command source.
"ON/OFF1" on a digital input can be combined with "ON reverse/OFF1" on another digital input.
1-64
Factory default setting
BOP (keypad)
Terminal
USS on RS232
Fieldbus
Digital input disabled
ON/OFF1
ON reverse /OFF1
OFF2
- coast to standstill
OFF3
- quick ramp-down
Fault acknowledge
JOG right
JOG left
Reverse
MOP up (increase frequency)
MOP down (decrease frequency)
Fixed frequency selector bit0
Fixed frequency selector bit1
Fixed frequency selector bit2
Fixed frequency selector bit3
DC brake enable
Enable PID
External trip
Disable additional freq setpoint
Enable BICO parameterization
P-Group: Commands
Active: NO
Max
6
P-Group: Commands
Active: NO
Max
99
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Data type: Unsigned16
Data set: CDS
Factory setting
6
Data type: Unsigned16
Data set: CDS
Factory setting
1