Siemens Sinamics G120 Series Parameter Manual page 41

Hide thumbs Also See for Sinamics G120 Series:
Table of Contents

Advertisement

p0300[0...2]
Select motor type / Select motor type
PM250
Access level: 2
PM260
Quick comm. YES
Can be changed: C
Min
1
Description:
Selects motor type.
This parameter is required during commissioning to select motor type and optimize inverter performance.
Most motors are asynchronous; if in doubt, use the following formula .
60 * P0310 / P0311 (the ratio of rated frequency (P0310) and rated motor speed (P0311)
If the result is a whole number, the motor is synchronous.
Values:
1:
2:
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
If synchronous motor is selected, the following functions are not available:
P0308 Power factor
P0309 Motor efficiency
P0346 Magnetization time
P0347 Demagnetization time
P1335 Slip compensation
P1336 Slip limit
P0320 Motor magnetizing current
P0330 Rated motor slip
P0331 Rated magnetization current
P0332 Rated power factor
P0384 Rotor time constant
P1200, P1202, P1203 Flying start
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Asynchronous rotational motor
Synchronous rotational motor
P-Group: Motor
Active: NO
Max
2
Parameters
List of Parameters
Data type: Unsigned16
Data set: DDS
Factory setting
1