r0053.1...15
CO/BO: Act. status word 2 / Act StatWd2
PM250
Access level: 2
PM260
Unit: -
Description:
Displays second status word of inverter (in bit format).
Bit field:
Bit
Signal name
01
f_act > P2167 (f_off)
02
f_act > P1080 (f_min)
03
Act. current r0027 >= P2170
04
f_act > P2155 (f_1)
05
f_act <= P2155 (f_1)
06
f_act >= setpoint (f_set)
09
Ramping finished
10
PID output r2294 == P2292 (PID_min)
11
PID output r2294 == P2291 (PID_max)
14
Download Dataset 0 from AOP
15
Download Dataset 1 from AOP
Notice:
r0053 Bit01 "f_act > P2167 (f_off)" ==> see parameter P2167
r0053 Bit02 "f_act > P1080 (f_min)" ==> see parameter P1080
r0053 Bit03 "Act. current r0027 >= P2170" ==> see parameter P2170
r0053 Bit04 "f_act > P2155 (f_1)" ==> see parameter P2155
r0053 Bit05 "f_act <= P2155 (f_1)" ==> see parameter P2155
r0053 Bit06 "f_act >= setpoint (f_set)" ==> see parameter P2150
r0054.0...15
CO/BO: Act. control word 1 / Act CtrlWd1
Access level: 3
Unit: -
Description:
Displays first control word of inverter (in bit format) and can be used to diagnose which commands are active.
Bit field:
Bit
Signal name
00
ON/OFF1
01
OFF2: Electrical stop
02
OFF3: Fast stop
03
Pulse enable
04
RFG enable
05
RFG start
06
Setpoint enable
07
Fault acknowledge
08
JOG right
09
JOG left
10
Control from PLC
11
Reverse (setpoint inversion)
13
Motor potentiometer MOP up
14
Motor potentiometer MOP down
15
CDS Bit 0 (Hand/Auto)
Notice:
r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
P-Group: Commands
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
P-Group: Commands
1 signal
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: Unsigned16
Data set: -
0 signal
FP
No
-
Yes
-
Yes
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
1-25